Pelco Security Camera C534M User Manual

®
System 9750  
Relay Interface  
CM9750-REL Series  
Relay Interface  
Installation/  
Operation Manual  
C534M (2/98)  
Pelco • 3500 Pelco Way • Clovis, CA 93612-5699 USA • www.pelco.com  
In North America and Canada: Tel (800) 289-9100 or FAX (800) 289-9150  
International Customers: Tel (1-559) 292-1981 or FAX (1-559) 348-1120  
 
1.0 GENERAL  
1.1 IMPORTANT SAFEGUARDS AND WARNINGS  
Prior to installation and use of this product, the following WARNINGS should be  
observed.  
1. Installation and servicing should only be done by Qualified Service Personnel  
and conform to all Local codes.  
2. Only use replacement parts recommended by Pelco.  
3. After replacement/repair of this unit’s electrical components, conduct a resis-  
tance measurement between line and exposed parts to verify the exposed  
parts have not been connected to line circuitry.  
The product and/or manual may bear the following marks:  
This symbol indicates that dangerous voltage constituting a  
risk of electric shock is present within this unit.  
This symbol indicates that there are important operating and  
maintenance instructions in the literature accompanying this  
unit.  
CAUTION:  
RISK OF  
ELECTRIC SHOCK.  
DO NOT OPEN.  
CAUTION:  
TO REDUCE THE RISK OF ELECTRICAL SHOCK,  
DO NOT REMOVE COVER. NO USER-  
SERVICEABLE PARTS INSIDE. REFER SERVICING  
TO QUALIFIED SERVICE PERSONNEL.  
Please thoroughly familiarize yourself with the information  
in this manual prior to installation and operation.  
Pelco Manual C534M (2/98)  
3
 
2.0 DESCRIPTION  
The Relay Interface units of the CM9750-REL Series provide up to 32 relay con-  
tacts for operating external equipment such as VCRs and lights. (The unit is shipped  
from the factory equipped with 16 outputs.) Each of the relays can be configured for  
normally open or normally closed operation by the placement of internal jumpers.  
The unit is shipped with the contacts in the normally open position. Each Relay  
Interface unit provides outputs for four GPIs (each GPI controls 8 relays). Refer to  
Figure 1 for the front and rear view of the unit.  
2.1 MODELS  
CM9750-REL16  
Provides 16 relay outputs. Includes transformer to convert 120  
VAC to 24 VDC.  
CM9750-REL16-X Same as CM9750-REL16 except has 230 VAC transformer.  
System 9750  
Relay Interface  
RELAYS 11 - 20  
RELAYS 1 - 10  
RELAYS 21 - 32  
POWER INPUT  
RELAY 32  
RELAY 1  
FUSE  
INPUT FROM  
CM9750/CM9760  
TYPICAL FOR ALL  
RELAY OUTPUTS  
Figure 1. Front and Rear Views of the CM9750/CM9760 Relay Interface Unit  
4
Pelco Manual C534M (2/98)  
 
2.2 CIRCUIT DESCRIPTION  
The Relay Interface consists of two relay cards (with additional room for two more),  
one motherboard, and one power supply board. The unit receives TTL level signals  
from the GPI SPINC card (located in the CM9750/CM9760 Controller) through the  
50-pin connector on the rear panel of the unit. This TTL signal is then inverted and  
applied to the corresponding relay to close the contact. The position of the strap  
determines the condition of the output. Refer to Figure 2.  
JUMPER  
3
NC  
NO  
2
RELAY  
1
OUTPUT  
COM  
TYPICAL FOR ALL  
RELAY CIRCUITS  
TTL IN  
+12 VDC  
RELAY  
MAX DC CURRENT 1 AMP  
Figure 2. Relay Output Functional Schematic  
Pelco Manual C534M (2/98)  
5
 
3.0 INSTALLATION  
3.1 MOUNTING INSTRUCTIONS  
NOTE: The Relay Interface unit can  
be configured to provide either nor-  
mally open or normally closed relay  
outputs. The unit is shipped with all  
outputs in the normally open mode  
of operation. If you need to configure  
outputs for normally closed opera-  
tion, refer to Sections 3.5 and 3.6  
prior to mounting the unit.  
The Relay Interface mounts in a 19-inch (48.26 cm) rack using standard mounting  
hardware. The unit occupies 1 rack unit (1.75 in. or 4.45 cm) of vertical space. The  
unit operates on TTL signals from the Controller. Because of distance limitations,  
the unit must be mounted in the same rack as the Controller for proper operation.  
3.2 CONNECTING TO THE CONTROLLER  
The unit comes equipped with a pretested, 3-foot (0.91m) ribbon cable to connect  
to the SPINC card located in the Controller. Prior to connecting the equipment, refer  
to the Controller Manual for installation information.  
To connect the two pieces of equipment, connect the supplied cable to the 50-pin  
connectors located on the Relay Interface and the Controller. Refer to Table A for  
the connector pin assignments.  
3.3 CONNECTING POWER  
The unit comes equipped with a 120 VAC or 230 VAC to 24 VDC wall-mount trans-  
former. Plug the transformer into an appropriate location and connect the other end  
to input connector on the rear of the unit. The unit is operational once power is  
applied to the unit.  
Table A. 50-Pin Connector  
Function  
Pin  
Function  
Pin  
+5V  
+12V  
NC  
NC  
50  
49  
48  
47  
46  
45  
44  
43  
42  
41  
40  
39  
38  
37  
36  
35  
34  
33  
32  
31  
30  
29  
28  
27  
26  
+5V  
-12V  
NC  
NC  
25  
24  
23  
22  
21  
20  
19  
18  
17  
16  
15  
14  
13  
12  
11  
10  
9
8
7
6
5
4
3
2
1
NC  
GND  
GPI 1 (8)  
GPI 1 (6)  
GPI 1 (4)  
GPI 1 (2)  
NC  
GPI 2 (8)  
GPI 2 (6)  
GPI 2 (4)  
GPI 2 (2)  
NC  
GPI 3 (8)  
GPI 3 (6)  
GPI 3 (4)  
GPI 3 (2)  
NC  
GPI 4 (8)  
GPI 4 (6)  
GPI 4 (4)  
GPI 4 (2)  
GND  
GPI 1 (7)  
GPI 1 (5)  
GPI 1 (3)  
GPI 1 (1)  
GND  
GPI 2 (7)  
GPI 2 (5)  
GPI 2 (3)  
GPI 2 (1)  
GND  
GPI 3 (7)  
GPI 3 (5)  
GPI 3 (3)  
GPI 3 (1)  
GND  
GPI 4 (7)  
GPI 4 (5)  
GPI 4 (3)  
GPI 4 (1)  
GND  
6
Pelco Manual C534M (2/98)  
 
3.4 WIRING THE RELAY OUTPUTS  
Refer to Figure 3. Select the desired relay output and insert the wires to be used  
into the square holes in the terminal. Tighten the screws until the wires are properly  
secured.  
3.5 INSTALLING AND REMOVING THE RELAY CARDS  
To install or remove any of the relay cards, remove the top cover to the unit. Refer to  
Figure 4 for the identification of each board.  
To remove a specific board, remove the mounting hardware (four Phillips screws)  
and disconnect the two ribbon cables connecting the relay card to the mother board.  
The card can now be removed from the unit.  
3.6 CHANGING THE JUMPER LOCATIONS  
Remove the desired board(s) as described Section 3.5.  
NOTE: Each board is the same and  
therefore has the same silkscreen  
identification for the relays and jump-  
ers.  
Next, determine which output you wish to change. Once decided, refer to Table B  
for the corresponding board and jumper.  
Once the proper board has been determined, gain access to the desired jumper and  
place in the desired setting. Refer to Figure 5 for the jumper pin assignments.  
INSERT CONNECTIONS  
FROM EXTERNAL EQUIPMENT  
RELAY 32  
TYPICAL FOR ALL  
RELAY OUTPUTS  
Figure 3. Wiring External Equipment to the Relay Outputs  
BOARD A (OUTPUTS 1-8)  
BOARD C (OUTPUTS 17-24)  
POWER SUPPLY  
BOARD  
BOARD B (OUTPUTS 9-16)  
BOARD D (OUTPUTS 25-32)  
Figure 4. Relay Card Location  
Pelco Manual C534M (2/98)  
7
 
Table B. Relay/Jumper Reference Chart  
Relay  
Board/Jumper  
GPI  
Relay  
Board/Jumper  
GPI  
1
2
3
4
5
6
7
8
A/J1  
A/J2  
A/J3  
A/J4  
A/J5  
A/J6  
A/J7  
A/J8  
B/J1  
B/J2  
B/J3  
B/J4  
B/J5  
B/J6  
B/J7  
B/J8  
1 (1)  
1 (2)  
1 (3)  
1 (4)  
1 (5)  
1 (6)  
1 (7)  
1 (8)  
2 (1)  
2 (2)  
2 (3)  
2 (4)  
2 (5)  
2 (6)  
2 (7)  
2 (8)  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
C/J1  
C/J2  
C/J3  
C/J4  
C/J5  
C/J6  
C/J7  
C/J8  
D/J1  
D/J2  
D/J3  
D/J4  
D/J5  
D/J6  
D/J7  
D/J8  
3 (1)  
3 (2)  
3 (3)  
3 (4)  
3 (5)  
3 (6)  
3 (7)  
3 (8)  
4 (1)  
4 (2)  
4 (3)  
4 (4)  
4 (5)  
4 (6)  
4 (7)  
4 (8)  
9
10  
11  
12  
13  
14  
15  
16  
P1  
P2  
RELAY 4  
RELAY 5  
RELAY 6  
RELAY 7  
RELAY 8  
J5  
J6  
J7  
J8  
J4  
J3  
J2  
J1  
RELAY 3  
RELAY 2  
RELAY 1  
1-2 = N/O  
2-3 = N/C  
1-2 = N/O  
2-3 = N/C  
PIN 1  
PIN 3  
PIN 2  
PIN 3  
PIN 2  
PIN 1  
(TYPICAL FOR JUMPERS  
ONE THROUGH FOUR)  
(TYPICAL FOR JUMPERS  
FIVE THROUGH EIGHT)  
NOTE: All straps are shown in the Normally Open Position.  
Figure 5. Relay Card Jumper Locations  
8
Pelco Manual C534M (2/98)  
 
4.0 OPERATION  
There are no specific operating instructions for the unit. The unit begins operation  
once power is applied. All operating commands are issued from the appropriate  
CM9750/CM9760 Keyboard(s) as defined in the Setup File. For additional informa-  
tion on the operation of the Relay Interface unit (GPI relays), refer to the Operation  
Manual or to the System Administrator Manual.  
Pelco Manual C534M (2/98)  
9
 
5.0 MAINTENANCE  
5.1 REPLACING THE FUSE  
WARNING: Always re-  
place a blown fuse with a  
fuse of the same rating. Fail-  
ure to do so could result in  
serious damage to the unit.  
The unit is equipped with a 2A fuse on the input. The fuse holder is located on the  
rear panel of the unit. To replace the fuse, first remove power to the unit by discon-  
necting the power at the wall socket. Rotate the fuse holder counterclockwise until  
the fuse holder comes out of its receptacle. Replace the fuse.  
10  
Pelco Manual C534M (2/98)  
 
NOTES  
Pelco Manual C534M (2/98)  
11  
 
6.0 WARRANTY AND RETURN INFORMATION  
WARRANTY  
Pelco will repair or replace, without charge, any merchandise proved defective in material or  
workmanship for a period of one year after the date of shipment.  
Exceptions to this warranty are as noted below:  
Five years on FT/FR8000 Series fiber optic products.  
Three years on Genex® Series products (multiplexers, server, and keyboard).  
Three years on Camclosure® and fixed camera models, except the CC3701H-2, CC3701H-2X,  
CC3751H-2,CC3651H-2X,MC3651H-2,andMC3651H-2Xcameramodels,whichhaveafive-  
year warranty.  
Two years on standard motorized or fixed focal length lenses.  
Two years on Legacy®, CM6700/CM6800/CM9700 Series matrix, and DF5/DF8 Series fixed  
dome products.  
Two years on Spectra®, Esprit®, ExSite, and PS20 scanners, including when used in  
continuous motion applications.  
Two years on Esprit® and WW5700 Series window wiper (excluding wiper blades).  
Eighteen months on DX Series digital video recorders, NVR300 Series network video  
recorders, and EnduraSeries distributed network-based video products.  
One year (except video heads) on video cassette recorders (VCRs). Video heads will be  
covered for a period of six months.  
Sixmonthsonallpanandtilts,scannersorpresetlensesusedincontinuousmotionapplications  
(that is, preset scan, tour and auto scan modes).  
Pelco will warrant all replacement parts and repairs for 90 days from the date of Pelco shipment.  
AllgoodsrequiringwarrantyrepairshallbesentfreightprepaidtoPelco,Clovis,California.Repairs  
made necessary by reason of misuse, alteration, normal wear, or accident are not covered under  
this warranty.  
Pelco assumes no risk and shall be subject to no liability for damages or loss resulting from the  
specific use or application made of the Products. Pelco’s liability for any claim, whether based on  
breach of contract, negligence, infringement of any rights of any party or product liability, relating  
totheProductsshallnotexceedthepricepaidbytheDealertoPelcoforsuchProducts. Innoevent  
will Pelco be liable for any special, incidental or consequential damages (including loss of use, loss  
of profit and claims of third parties) however caused, whether by the negligence of Pelco or  
otherwise.  
The above warranty provides the Dealer with specific legal rights. The Dealer may also have  
additional rights, which are subject to variation from state to state.  
Ifawarrantyrepairisrequired, theDealermustcontactPelcoat(800) 289-9100or(559)292-1981  
to obtain a Repair Authorization number (RA), and provide the following information:  
1. Model and serial number  
2. Date of shipment, P.O. number, Sales Order number, or Pelco invoice number  
3. Details of the defect or problem  
If there is a dispute regarding the warranty of a product which does not fall under the warranty  
conditions stated above, please include a written explanation with the product when returned.  
Methodofreturnshipmentshallbethesameorequaltothemethodbywhichtheitemwasreceived  
by Pelco.  
RETURNS  
In order to expedite parts returned to the factory for repair or credit, please call the factory at (800)  
289-9100 or (559) 292-1981 to obtain an authorization number (CA number if returned for credit,  
and RA number if returned for repair).  
All merchandise returned for credit may be subject to a 20% restocking and refurbishing charge.  
Goods returned for repair or credit should be clearly identified with the assigned CA or RA number  
and freight should be prepaid. Ship to the appropriate address below.  
If you are located within the continental U.S., Alaska, Hawaii or Puerto Rico, send goods to:  
Service Department  
Pelco  
3500 Pelco Way  
Clovis, CA 93612-5699  
If you are located outside the continental U.S., Alaska, Hawaii or Puerto Rico and are instructed  
to return goods to the USA, you may do one of the following:  
If the goods are to be sent by a COURIER SERVICE, send the goods to:  
Pelco  
3500 Pelco Way  
Clovis, CA 93612-5699 USA  
Pelco, the Pelco logo, Camclosure, Esprit,  
Genex, Legacy, and Spectra are registered  
trademarks of Pelco.  
If the goods are to be sent by a FREIGHT FORWARDER, send the goods to:  
Pelco c/o Expeditors  
473 Eccles Avenue  
South San Francisco, CA 94080 USA  
Phone: 650-737-1700  
Fax: 650-737-0933  
Endura and ExSite are trademarks of Pelco.  
© Copyright 1998, Pelco. All rights reserved.  
12  
Pelco Manual C534M (2/98)  
 

Philips Camera Accessories SCE4430 User Manual
Philips Cell Phone 21A582BH User Manual
Philips Stereo System FW V720 User Manual
Philips TV Cables SWA2138 User Manual
Philips Universal Remote SRU3006L 27 User Manual
Philips VCR NV MV41GN User Manual
Planar Car Video System PL2410W User Manual
Planar Computer Monitor PL1711M User Manual
Planet Technology Switch FNSW 4800 User Manual
PNY Computer Hardware FX 1700 User Manual